1. My heater is not heating, but
the pump is running, is the heater broken?
The heater may not be broken. The first thing you will want to check
is for voltage present at the heater terminals. If voltage is
present at the element it is most likely bad and needs to be
replaced. If there is no voltage present follow the plumbing from
the end of the heater to the tub return. Is there any restriction
device such as a filter past the heater? If not, your problem may be
lack of restriction. Heaters have pressure switches mounted on them
to test for an expected backpressure to allow for the heater to come
on. With out the expected backpressure the heater will not activate.
In some cases the placing of an eyeball restrictor in the return to
the tub will allow for enough restriction to allow the heater to
work. In others a filter may need to be added.
2. The hi-limit is tripping before my
tub gets hot, should I just replace it?
You will want to verify the flow of water through the heater before
just replacing the limit switch. If the limit switch is tripped,
reset it and run the tub while calling for heat. Place your hand on
the heater housing. If the housing is getting hot before the water
in the tub it is generally a flow problem. Look at the returning
water to the tub. Does it appear to be moving? If not, remove the
filter and retry. You also may want to check where the limit switch
mounts to the heater and see if there is just a hot spot in the
heater. If there is an area of the heater housing that is getting
hotter than the rest, the element may be too close to the heater
sheathing and will need to be replaced.
3.
How can I replace two of the jets and some of the 2” flex line in my
spa if I can’t find a part number on the jets?
The jets you described are not uncommon. The only thing that is not
consistent is the 2” flex hose running to them. Most
jets come with
1-1/2" Inlets. Whenever you look to replace a jet, the actual
manufacturer or style is never as important as whether the jet fits
or not. The major factors for replacement are: A) Hole size - The
jet body must fit the hole in your tub. That means the wall fitting
needs to be the same size or larger than the one you are replacing
(you can always make the hole bigger). B) Plumbing size - Plumbing
can be reduced or stepped up but, to insure proper flow, it is best
if the plumbing size matches the inlets of the jet body. Remember
that flex tubing O.D. is always about 1/4" larger than the labeled
size (i.e. 1-1/2" flex measures about 1-3/4"). C) Orifice size –
This is important if you are replacing more than one jet. If you
have 6 jets with a 3/4" orifice and you replace them with 1/4" the
flow through those jets will have been restricted by more than half
the original value. This can cause priming and/or heating (High
Limit) problems. D) Color and style – Obviously, this is of no
concern operationally. Having said that, installing a "green" jet in
a "pink" spa may sharply reduce the perceived value. If the old jet
was a pulsing or spinning type and the replacement is simply a fixed
orifice the customer is not likely to see the value in the new jet.
4. I replaced a bad heater coil
and broken pressure switch but there is still no heat to the tub.
What else could be wrong?
First check incoming power (L1 to L2 for 240v and both hot legs to
Neutral for 110v) to insure proper voltage is reaching the control.
Next, go to the heater element and measure for voltage reaching the
element. If you have voltage at the element then we need to
determine whether the element is capable of heating. The easiest way
to accomplish this is to kill the power, disconnect both wires to
the element, and measure the resistance across it. You should get
between 9 and 12 ohms resistance. Failure to get continuity across
the element indicates the filament is broken and the element is bad.
Good resistance indicates the element is capable of heating and the
problem is likely that the heat is not reaching the tub due to poor
flow. Check the valves, adjustable jets, and filter. No voltage
reaching the element indicates another component problem inside the
control. Trace the heater supply wires back until you find the
heater voltage. The component or connection immediately after the
point you find the voltage is the issue. Remember that in the case
of a relay or contactor the fact that the device does not switch may
have nothing to do with the relay or contactor itself. Check to
insure the coil is getting voltage to switch the contacts. If there
is voltage but the unit does not switch the relay or contactor is
bad. If there is no voltage at the coil then you must follow the
coil wires back until you find the voltage and determine why it is
not reaching the contactor or relay coil.
5. I am plumbing a spa with a
5.5kW flow-thru heater. Can the water flow through the heater from
either end?
As long as there isn't a flow switch in the heater it doesn't matter
which way the water flows. Flow switches are directional and
pressure switches are not. However, pressure switches have to be
installed on the output side (pressure side) of the pump while a
flow switch will work on either side. As far as the heater itself,
as long as it is filled with moving water it doesn't matter which
direction it flows.
6. Why does my Balboa spa side
read like Chinese when I replace the PCB with a generic replacement?
When you replace a factory specific PCB, such as Jacuzzi, with a
generic replacement, like a Balboa 54122, it is sometimes necessary
to change the filter cycle jumper from the A to B mode. This will
change the characters to the correct symbols. At the same time it
will also be necessary to remove the battery jumper for 15-30
seconds to allow the board to recognize the mode jumper change.
7.
How do you fix a leak when it is not visible from the access panels?
In my experience the only sure way to fix a leak is to identify the
location of the leak and replace the section of plumbing or repair
the connection that is leaking. To find out where the leak is
requires a couple of steps and none of these are going to be quick
and easy. First check the pumps. Pump seals are a consumable item
and will wear out sooner or later. Do this with the power off as the
problem is often masked when the pump is running. Next, if the
skirting is removable you are going to want to take it all off. If
you are lucky you will be able to see the leak once all the skirting
is off. However, in most cases the sprayed in foam will just about
eliminate any possibility of that. Sometimes you can follow the
moisture in the foam to where the leak starts but because of
capillary action this gets to be real fun also. Go to the grocery
store and buy a couple of packages of clothing die. Dump that in the
water and let it run for a day. After that you can often see the
color trail left by the die with minimal digging in the foam. If you
can't find the source or the skirting is not removable you're going
have to drain the tub and tip it up to find out where the leak is.
You have got to work quickly once you do this because gravity is now
going to make the die move to strange locations as the tub sits on
its side. Remember that in most cases the water is always going to
travel down from where the leak is. Pay close attention to the "jet
to tub" connections and the suction fitting gaskets. Repair of
anything is likely to require disassembly and replacement of the
failed part (i.e. cracked, broken, misaligned, etc.) This also
usually requires cutting and gluing of the plumbing in addition to
the component that is having the problem.
8. Pump makes a humming sound
but will not run. Any suggestions?
It sounds as if we have the wrong voltage reaching the
pump motor
(i.e. 120v reaching a 240v motor). The motor should have the voltage
listed on its label. Using a voltmeter check the voltage at the
receptacle of the control.
9. What would cause an electric
heating element to short out with the water and trip the GFCI?
More than likely what you are experiencing is a pinhole failure of
the element sheath. This can occur in one of a couple of
circumstances. If there was any trapped air in the manifold when the
heater was on (I'm talking about the size of the end of your pinky)
that area of the sheath can super heat and a fracture can develop in
that location. This can also occur if the water does not move
through the manifold at the correct speed. Low flow condition
(closed valve, dirty filter) does not need air to cause an over heat
as the water in the manifold boils and creates its own bubble from
steam. Another is chemical damage. Low PH indicates that the water
is acid and sooner or later it will attack the sheath and cause a
pinhole failure. Scaling from total alkalinity being out of
tolerance is another way to cause a "hot spot" fracture due to the
deposits being left on the element isolating it from the water so
heat transfer cannot happen correctly.
10. The heat status light
flashes after the selected temperature is reached. When it does this
nothing operates indicating a bad temp or hi limit sensor.
Think you have the right idea but the wrong solution. However, you
are not alone. Whenever there is a
High Limit issue the first thing
many people believe is that the sensor or switch is bad rather than
that it is doing exactly what it is meant to do!
The flashing light is telling you is that one of the sensors is
reading an over temp condition. While a bad sensor is a possibility
it is seldom my first choice. Since a high limit failure is a safety
issue, I try to convince everyone to believe that the issue is
"real" rather than caused by a faulty component.
First
check the water movement. It may not be moving enough to exchange
heat in the manifold correctly. This means that we are heating
without the pump on or with insufficient water flow. Secondly, check
for a bad device, which should only be considered after you have
verified that water flow is not the issue.
Typical causes for improper heat transfer include:
1) A dirty filter. Easily verified by removing the element from
the canister and running the unit as normal. If the unit no longer
errors out that’s the problem no matter how "clean" it looks.
2) Closed or broken valves. You would be surprised how many
people just forget to open the valves after servicing. Some slice
valves can also become loose and slide closed due to vibration.
3) Too many adjustable jets closed down to minimum flow.
4) Clogged or broken pump impeller.
5) Air lock in the plumbing.
As you may have guessed by now the common thread in this
situation is poor or no flow. Because they can see the water moving
many technicians dismiss this as the actual issue. I like to use the
"touch test" to determine whether you should worry about this. If
the manifold is hotter to the touch than the water in the tub is (on
a single two speed pump system) then you have a flow problem! This
test does not work for "circ" systems where the low flow heaters
often feel hotter than the tub water. Fortunately most of these
systems will have a "flow" error if this issue exists.
The second part of this issue is just as often overlooked and
specific to units like Balboa that only break one leg of the heater
current for temp control. Heating with no pump at all sounds
ridiculous but can happen if the output device fails "on" (stuck
contacts on relays or contactors). Check for voltage reaching both
heater terminals at the same time with the pump disconnected and the
thermostat turned down. If voltage is present replace PCB or output
relay.
There is also a little understood condition that happens when an
element has a short to ground and one leg of heater voltage remains
connected. Now we would hope that the GFCI would see this and trip
off. However, I have seen this situation cause the OH or flashing
LED issue more than once when the GFCI did not indicate any problem
at all. As long as the power consumed does not exceed 5ma (60watts)
you will never see a GFCI issue but 60 watts is more than enough to
cause an OH in a small, enclosed manifold with no moving water. The
GFCI can also be bad but that’s another issue. Check the heater for
a short to ground by using a meter capable of reading in the
20-30Meg Ohm range. Measure the resistance between the heater
terminal and ground (the metal manifold, nut or plate that holds the
element) you should get no resistance at all (i.e. the 1 on the left
side of the display or OL on the meter display). Any actual numbers
at all indicates a connection to ground and a bad element. and that
can cause the OH problem. In any event if you have a shorted heater
it must be replaced.
That is probably more info than you ever wanted on High Limit
failures. Hope it helps. |