Once you select the correct scale and type of value to be measured,
it is important to realize what the meter actually does when you take
measurement. There is no magic involved but realizing what is actually
taking place can make the difference between accurately and safely
diagnosing reading and obtaining misleading information.
Continuity
/ Resistance
These two terms are often confused because they are similar in nature.
In both cases the actual mechanics Of the measurement is done by the meter
sending a voltage out over one lead and measuring the amount that is
picked up on the other lead. The meter selects the scale by dropping the
voltage through resistors (shunts) that are selected with the scales.
Lower voltage will be required to push through smaller resistance and
still show a value in the ranged of the display. (This is why
you should never measure resistance or continuity with the power on. It is
very easy to exceed the circuit capability, especially in 120/240
applications).
Continuity is a measurement of connection.
Any voltage returning within a certain range sounds tone. Unfortunately,
the operating range can be from zero up to a hundred ohms or more and can
give you misleading information. This measurement is seldom usable for
anything but detecting the presence of connection.
Resistance is a measurement of the opposition
to electron flow in a circuit. The value is expressed in ohms and gives
you the best representation of how good a connection is between two
points. When measuring to determine a good connection always use the
resistance scale to insure you can also diagnose the condition of the
connection rather than just the presence of connection.
Voltage
When measuring voltage the meter is performing a comparison between the
potential on the two leads. In other words, it measures the distance of
the voltage on the red vs. the black lead. Understanding this
is very important, as a zero reading does not necessarily mean there is no
voltage present. There can be 600 volts present in the
circuit, but if it is felt on both leads at the same time the display will
show zero. Another condition that should be watched for is when one of the
points measured is not part of the circuit. An open (loose wire, burned
contacts, bad coil) circuit will not have any value to the meter. There is
a large difference between zero volts and no connection. Once
again, just because the meter reads zero, don't assume there is no voltage
present. It is always advisable to double check for the
presence of voltage before attempting to service any unit. By checking the
ground (this is one of the few times when using ground as a measuring
point is advisable).
Current
The only time currant is present is in complete circuit.
Therefore, you cannot measure currant outside the circuit like you can
with voltage or resistance. Unless you have an inductive coil (clamp or
meter) it is necessary for the currant in the circuit to run through the
meter to measure it. The only way this can happen is to open the circuit
and put the meter in series with the currant flow. Unfortunately, most
meters can only handle half an Amp (500ma) in this manner. Although some
can handle up to 10 amps and/or have accessories that allow higher
readings. Exceeding the capability of the current monitoring circuit can
damage meters without this capacity.
|